Scottish Parliament Building gets fan upgrade

ebm-papst UK and Airedale International recently worked together to provide the Scottish Parliament Building with a reduction of approximately 50% in power consumption on its computer room cooling. Helen McHugh, head of sustainable technology at ebm-papst UK, outlines the project.

The reduction of around 50% was achieved by upgrading its Airedale aircon units to use ebm-papst UK EC fans. The result was in initial savings of 11.5 tonnes of carbon per year and a payback period of 21 months.

Further savings are expected when the second phase of this project is implemented, when overall financial savings of £13,500 per year are expected, with a reduction in carbon emissions of 20 tonnes per year.

The Scottish Parliament is dedicated to reducing both carbon footprint and energy bills, Environmental Performance Manager David Fairhurst has made significant  improvements to the building in recent years having already achieved a reduction in carbon emissions of 25%. Following a presentation by ebm-papst UK on energy savings possible on existing HVAC equipment by upgrading to EC fans, Mr Fairhurst approached ebm-papst UK and asked that a survey be carried out on the Parliament Building’s HVAC equipment.

ebm-papst UK identified the HVAC equipment that would offer the greatest potential for energy savings and by working together with the original equipment manufacturer, Airedale was able to provide the best solution.

It was decided that the computer room cooling offered the best potential for energy savings, therefore an initial trial was carried out on one Computuer Room Air Conditioning (CRAC) unit; following excellent results on the initial trial unit, further installations have been carried out on both CRAC and air handling units (AHUs).

Mr Fairhurst said: The Scottish Parliament is committed to reducing its carbon emissions by  more than 40% by 2020.  To achieve this we need to reduce electricity use by at least 40%.  ebm-papst UK claimed that its fans would deliver at least this level of reduction and this claim has been proved to be true. EC fans are a step change technology, much like LED lighting, which has been a very welcome addition to our carbon management plan”.

Site Survey

An initial site survey was carried out on the HVAC equipment, with measurements taken of power consumption and performance. Based on the data collected, ebm-papst UK was able to a design a suitable EC fan solution and produced estimates of energy savings and paybacks.

The site survey looked at CRAC units, AHUs and fan coil units, and based on the estimated energy savings it was decided that the initial trial be carried out on one of the Airedale CRAC units (DF50CW).

Trial Unit

The trial was carried out on an Airedale DF50CW downflow CRAC unit. Each computer room contains two air conditioning units, the majority of these being downflow units, which are installed on a raised floor.

The trial involved replacing the existing fan (AC belt driven blowers) with new EC backward curved RadiCal  fans, and also re-locating the fans into the floor void(*). The relocation of the fans into the floor void involved opening up the floor of the unit, and lowering the backward curved fans into the space, the EC fan is mounted in a custom frame which allowed for easy installation.

Once installed, the EC fans were set to meet the same airflow as the original AC fans - this was done by use of a simple potentiometer that provides a 0–10v control signal to the EC fans.

The current and power draw of the fans was then measured and compared with the original AC fans.

The trial resulted in a reduction in current draw of approximately 50%.

(*)For downflow units, if the floor void is deep enough, installing the fans in the floor void can provide additional energy savings due to the reduced operating pressure.

Full installation

Following the trial on DF50CW, which resulted in a reduction in current draw of approximately 50%, it was decided to continue and upgrade the fans in all the computer rooms.

A total of five computer rooms have now been upgraded with a single CRAC unit per room, however, each room has two CRAC units with one always on standby. The standby unit has not yet been changed to EC.

To achieve further energy savings ebm-papst UK has recommended that rather than have one unit on standby, a more efficient solution is to run both CRAC units at 50% performance (to give an overall matched airflow). Due to fan laws this will result in an additional 50% reduction in energy consumption for the same performance.

To satisfy the need for back-up in the event of one of the two units failing, the units will be linked via an upgraded Airedale control, which means tha the EC fans of one unit will automatically ramp-up to compensate for any failure of the fans in the other unit.

Results / Analysis

Power measurements were taken on all units before and after the upgrade to EC fans.

In all cases the airflow of the EC units was set to the same as the AC units.

Savings varied dependent on the size and number of fans per unit, the larger units which have two fans fitted showing more savings than the smaller units with only a single fan, however, the overall energy savings are still significant.

Measurements taken include: current draw, power draw and power factor.

Fan Type

Measurements

Annual figures

Current

Power

Power

Power

Carbon

Cost

(A)

Factor

(kW)

(kWh)

(T)

(£)

AC Fans

41.9

0.71

18.24

159,782

23.8

£15,978

EC Fans

15.2

0.91

9.38

82,169

12.2

£8,217

Savings

26.7

-0.2

8.86

77,613

11.6

£7,761

% Savings

 

49%

Note:

1 Due to the improved power factor of the EC fans, the reduction in current draw is considerably greater than the reduction in power, therefore the below table shows both figures.

2 Assumptions made for calculations:

Operation 8760hrs / year

Electricity cost 10p/kWh

kWh to CO2 conversion factor = 0.54522

CO2 to Carbon conversion factor = 0.2727

Summary of Savings

Text Box: Based on operation -   24 hours/day, 365 days/year

Savings (annual)	 	All five Units @ matched airflow 
Energy saving  )	       		49%		    	
Energy               (kWh)		77,614	                             
Value     	       (£)	            	 	£7,760		    	
Carbon  	       (T)	       		11.5		    	
Payback Period	             		21 months                    
 

It was also noted by the client that due to the higher efficiency of the EC fans, the motors run cooler and therefore the overall cooling load in the server rooms was reduced.

Further savings

In addition to the savings already achieved, further savings are expected by carrying out the following additional upgrade.

Running all units at 50% performance rather than leaving some on standby.

As mentioned, all comms rooms have two CRAC units, however only one of these operates at any one time, leaving the second unit on standby.

The proposal is to run both units at 50% performance. Based on making these changes the estimated energy savings will be as follows;

Saving  -  running 1 unit @ 100% performance - 49% (annual savings = 11.5T Carbon &   £7.7k)

Saving -  running 2 units @ 50% performance each - 85% (annual savings = 20   T Carbon &   £13.5k)

Conclusions

The initial upgrade of one CRAC unit per computer room has resulted in energy savings of approx. 50%, with an annual reduction of 11.5 tonnes of carbon and a financial saving in the region of £7,700 per year.

When the second phase of this upgrade has been completed and all CRAC units are running, rather than leaving half the units on standby, the estimated saving will be in the region of 20 tonnes of carbon and £13,500 per year.

The IOR Annual Conference – a conference on-demand

Delegates to the IOR Annual Conference taking place from 21 to 22 April will get the chance to access the event live and all sessions and recordings for up six months afterwards providing fantastic value and allowing anyone registering for the event ...

  01-Apr-2021

Thunder: the full inverter reversible R290 heat pump from 40 to 85 kW

Thunder is the newest solution from Clivet, designed with full-inverter technology on latest-generation scroll compressors and axial fans....

  24-Apr-2024

Customised Consulting TM44 Inspection Services

Customised Consulting are accredited to provide TM44 Inspection Services ((also known as Air Conditioning Energy Assessments (ACEA)) for both simple (level 3) and complex (level 4) systems for buildings and can provide competitive quotes in Weybridge, Surrey, Sussex, London and Kent.
  25-Apr-2024
ACR News is the number one magazine in the air conditioning and refrigeration industry. Don’t miss out, subscribe today!
Subcribe to ACR News

Diary

BESA National Conference