ACR-News

 

New IOR Guidance note available

The IOR has released a new guidance note on the Pressure Equipment (Safety) Regulations and Pressure Equipment Directive (GN36) outlining the requirements for installers of RACHP systems. 

In the RACHP sector all the components are supplied by a manufacturer for site installation (assembly) by a specialist third party contractor who might not realise that they then become the manufacturer of the assembly (an integrated and functional whole) under PE(S)R. 

With the move to R32 and other A2L refrigerants, classified as PE(S)R group 1 fluid (“dangerous”), this moves many systems from SEP (sound engineering practice) or hazard category 1 into hazard category 2 or higher. 

Systems which are category 2 or higher must comply with the PE(S)R and must be assessed by an approved Conformity Assessment Body or under an assessment scheme which has been certified by a Conformity Assessment Body.

Additional guidance on pressure and PED are also available for free from the IOR web site. Find out more and download the documents at ior.org.uk/buy-documents

 

Comments

Already Registered?
Sign In
Not Yet Registered?
Register

The IOR Annual Conference – a conference on-demand

Delegates to the IOR Annual Conference taking place from 21 to 22 April will get the chance to access the event live and all sessions and recordings for up six months afterwards providing fantastic value and allowing anyone registering for the event ...

  01-Apr-2021

Carrier UK installs Toshiba VRF at luxury hotel

Carrier Solutions UK has successfully supported a major refurbishment at The Reach Hotel in Manchester (formerly La Reserve Apartments), delivering a Toshiba Variable Refrigerant Flow (VRF) solution in collaboration with contractor AC Mechanical ...

  18-Aug-2025

Has your Chiller been checked for Refrigerant Leaks?

Has your Chiller been checked for Refrigerant Leaks?
  07-Aug-2025
https://www.acr-news.com/new-ior-guidance-note-available