Masterclass: Shell & Tube Evaporators-Part 17

In the last article we looked at shell and tube water chillers and other types of water chiller evaporators. This month we conclude our study of the major refrigeration components by looking at Baudelot coolers and liquid refrigerant receivers.

Mike Creamer.

Baudelot cooler

A variety of applications require a fluid to be cooled to a temperature very close to the freezing point. Baudelot coolers are therefore commonly found in industrial refrigeration, dairy and a variety of food cooling applications. Wine and wort cooling can also be achieved with this type of cooler.

The Baudelot cooler comprises a set of horizontal refrigerant tubes very similar in format to a conventional air-to-refrigerant evaporator coil. However, this type of liquid cooler exposes the liquid to the atmosphere. The refrigerant passes through the tubes in the same way as heat exchangers described previously. The liquid to be cooled passes over the outside of the refrigerant tubes in the form of a thin liquid film thus causing aeration of the liquid which can be advantageous in certain food cooling applications.

If freezing of the liquid should occur, there will be no damage to the evaporator tubes as these are not confined within a shell which would otherwise cause collapse and fracture of the tubes due to the anomalous expansion of water.

The liquid to be cooled is fed to the upper section of the Baudelot cooler via a distributor arrangement to ensure equal supply of liquid over the bundle of evaporator tubes. A collection tray at the base of the evaporator collects the chilled liquid. The cooler can be insulated by surrounding walls in order to maintain high efficiency. Ammonia is very often used with this type of cooler. This requires a gravity feed system from a surge drum located above the chiller. The level of refrigerant within the drum is maintained by a simple float control.

Shell and coil cooler

The shell and coil cooler is very simple in concept and construction. The refrigerant runs within a simple helical coil submersed in an enclosed vessel containing the liquid to be cooled. The refrigerant coil can also be attached to the exterior of the vessel. Although this will reduce the heat transfer efficiency, fracture of the refrigerant coil with subsequent release of refrigerant will prevent injection of the refrigerant into the liquid to be cooled which may be a concern in food-related applications.

Unlike the conventional shell and tube evaporator where the volume of water is relatively low in relation to the tube bundle, the shell and coil cooler has a large body of liquid compared to the size of the refrigerant coil. This large body of water can serve as a useful buffer to meet transient heat loads or to provide a limited amount of cooling time in the event of refrigeration system failure.

The cleaning of the liquid chamber in a dry expansion shell and tube evaporator is not possible unless the tube bundle is removed or cleaned by chemical means. Cleaning of the shell and coil cooler is normally simple to achieve. This type of liquid chilling heat exchanger is usually confined to small capacity applications.

Co-axial evaporators This type of heat exchanger consists of a tube concentrically positioned within a larger tube. The entire arrangement is then normally wound into a helical coil to form a compact heat exchanger assembly. This type of heat exchanger is also very often used as a condenser, particularly in small unitary reverse cycle heat pump products. The refrigerant usually flows through the inner tube and the water/fluid through the outer annulus, although this arrangement is reversed on certain products. When used as an evaporator, the liquid refrigerant is injected at the base of the helix thus allowing the vaporised refrigerant to leave at the top connection. This is reversed when applied as a condenser. It is also possible to arrange the water/liquid flow to run parallel with the refrigerant flow or contra flow. The external tube is rated for 10bar maximum and -20ºC to +100ºC. The internal tube is rated for 26.5bar maximum and -30ºC to +100ºC.

Liquid refrigerant receivers

Refrigerant receivers are only installed in a refrigerant system when absolutely necessary in order to maintain simplicity and avoid excess cost. Receivers require a minimum operating refrigerant charge which adds to the overall system charge, cost and increased losses in the event of a major leak. The liquid refrigerant receiver, situated on the discharge side of the condenser to “receive” refrigerant as a sub-cooled liquid, is normally fitted for the following reasons:

1. On larger systems it will be necessary to temporarily store the total system refrigerant charge or a portion of the refrigerant charge whilst carrying out service or repairs on part or the whole of the system. In some water-cooled condenser systems, the condenser also serves as a receiver, provided the total refrigerant charge does not exceed its storage capacity, in which case a separate receiver will be installed. The receiver must be selected to hold the full system refrigerant charge when only 80% full to avoid risk of explosion when an increase of refrigerant temperature occurs. The 20% free volume will allow the refrigerant liquid to expand into the gaseous region without problem. The receiver acts as a storage point from where the refrigerant is discharged to the thermostatic expansion valve(s). To ensure that only liquid is discharged, the receiver will have a dip-tube fitted to pick up liquid refrigerant from the bottom of the vessel. Any gas will build up at the top of the vessel and is prevented from exiting the receiver by a sealing charge dependent on diameter of the vessel and connection size. A typical receiver configuration is shown in Fig 1.

2. On systems utilising multiple evaporators, where the liquid refrigerant normally present in an evaporator is not required at low-load or off-stage conditions, a receiver is require allowing the unused refrigerant to be held elsewhere other than the condenser.

3. On systems requiring pump-down operation, where the refrigerant in one or more evaporators is completely evacuated when the load is satisfied, a receiver is used to hold the excess refrigerant charge. The receiver will be designed to hold the entirety of the operative charge plus a percentage determined at the selection stage. This is covered in the relevant section below.

4. The receiver provides a housing for the systems over pressure protective and safety devices. These can take the form of:

Fusible plug Bursting disc Safety relief valve

The type of safety device fitted depends on the capacity of the system.

5. Receivers accommodate the excess refrigerant due to fluctuating charge in the low and high pressure sides of a system and allow the condenser to be virtually free of liquid thus maximising the effective condensing surface and overall efficiency of the condenser and the system as a whole. Liquid refrigerant in the receiver normally experiences further sub-cooling with attendant benefits to system efficiency.

6. On systems using air-cooled condensers, receivers provide sufficient refrigerant to ensure the liquid line(s) are completely full of liquid refrigerant on start-up to avoid starvation of the TEV and evaporator which would otherwise lead to cycling/shutdown through tripping of the low pressure cut out.

figure 1
 

Positioning

The liquid receiver should be positioned as closely as possible to the condenser with the interconnecting pipework arranged to allow free drainage from condenser to the receiver. The pipework must not cause excessive friction pressure loss or gas binding and must have adequately sized valves and fittings. Positioning of the receiver is also dependent on the type of installation. The installer is usually left to decide on the receiver’s ultimate positioning. Some factors that may influence this decision are the size of the compressor pack, length of discharge line from relief valve, ambient temperatures and increased sub-cooling requirements. Siting that will allow the receiver to be exposed to direct solar radiation must be avoided. When installed internally, do not site near steam pipework or high temperature plant. Excess heating of the receiver will diminish plant efficiency and would be dangerous if the receiver were too full.

If the receiver is installed outdoors and the plant is required to operate in winter, it may be necessary to install trace heaters to maintain adequate pressure in the receiver in order to avoid system problems at start up.

Securing/mounting

There are two basic mounting options for receivers:

Stud mounting: A stud is provided to enable the installation team to secure the receiver to a plinth. This method is predominantly used when the receiver is part of a multiple compressor pack.

Leg/bracket mounting: This provides for the most stable mounting and is used for stand-alone receivers for large installations. Compressor mounting plates can also be fitted on request.

Maintenance

A liquid receiver is a pressure vessel and must be treated with care and in accordance with current regulations and directives. Support the receiver clear of the floor to avoid contact with ground surface water which will lead to corrosion and ensure it is level. The receiver should also be protected from corrosive atmosphere and shielded against physical damage, particularly from heavy vehicles and falling objects. Routine inspection, periodic cleaning and painting is strongly recommended.

Capacity range

The receiver is rated on its capacity to hold the “pump-down” charge (kg). Receivers from manufacturers can range from 1.6kg to 1000kg pump-down based on standard catalogue figures at a temperature of 40ºC (104ºF) for HCFC22. In addition to the standard capacity receivers, OEM models are available to hold any charge.

Construction

Basically, the receiver is a holding tank and, as such, is fairly simple in construction. There are four types of part in the assembly.

1. The shell, made from seamless steel tube.

2. The end caps, made for drawn steel plate.

3. The connection bosses, made from steel billet. 4. The dip tube and nozzles, made from ERW or seamless drawn tube.

Assembly of these parts is achieved by welding to exacting standards by suitably qualified personnel. Design, manufacture and assembly of receivers must conform to the various pressure vessel rules and regulations governing the country in which they are to be used. There are generally only two types of liquid receiver (horizontal and vertical). The vertical receiver is more common on compressor packs in order to reduce the footprint of the equipment, particularly where floor space is restricted.

Design

The first step of the design function is to establish the type of receiver required, ie vertical or horizontal. The receiver must then be sized for the pump-down capacity including the safety margin allowance. The maximum operating charge must be determined for the system plus a percentage for long runs of suction, liquid and discharge pipework. It is essential that the maximum operating charge be determined taking into consideration, for example, the winter charge in an air cooled condenser having flooded head pressure control, this being much greater than normal summer charge.

The storage capacity of the receiver is then based on the liquid occupying no more than 90% of the internal volume when the temperature of the refrigerant is 40ºC. The final capacity of the receiver should always be greater than the sum of the maximum operating charge plus the sealing charge, which is dependent on vessel diameter and connection size.

The sealing charge prevents gaseous refrigerant from escaping downstream by ensuring that when the system is fully utilising the design refrigerant charge, there is still a small amount left at the base of the receiver to ensure only liquid leaves the receiver thus providing the expansion device with liquid only. The table below defines the sealing charge as a percentage of pump down capacity.

Summary:

 

 


The resultant capacity must then be converted to an internal volume for the refrigerant to be used. At the maximum operating temperature/pressure, a given amount of the liquid refrigerant will occupy a specific volume (m3/kg), obtainable from the pressure/enthalpy chart or tables of refrigerant thermo-physical properties for the relevant refrigerant. Density (kg/m3) can also be used in these calculations.

Design code

The next important step is to establish the design code to be used. Vessels are designed in accordance with the category they fall into. Vessels are classified by pressure multiplied by volume, P x V. A typical example of classification by the product of pressure and volume is shown in Fig 2.

Receiver ancillary equipment

Typical equipment installed as part of the receiver package can include: pressure relief devices; inlet and outlet valves; sight-glass; liquid level column; dial level indicator; liquid level switch (electronic output); cool gas connection; heat exchangers.

In order to ensure unrestricted flow from the condenser to the receiver, the pressure in the receiver must be lower than that at the condenser outlet. Alternatively, the elevation of the condenser above the receiver must allow a refrigerant column high enough to overcome the pressure difference. In addition, the refrigerant piping diameter from the condenser to the receiver must be of adequate diameter to ensure minimal friction loss.

The receiver and the pipework leading to it must provide a free flow of liquid from the condenser to the receiver by equalising the pressures between each so that the receiver is not able to build up a higher pressure than the condenser. This can be achieved by ensuring that the condenser drain line is sized and arranged to allow liquid to flow out of the condenser whilst allowing gas from the receiver to pass in the opposite direction to the condenser. The drain line should be sized to achieve no more than 0.5-0.75m/s liquid velocity. Piping should have adequate downhill slope without liquid traps.

Alternatively, the drain line between the condenser and receiver can be fitted with a separate vent line to permit receiver and condenser pressures to equalise, although the discharge gas from the compressor must be prevented from entering the vent line by fitting a non-return valve in the vent line.

 

figure 3
 

 


NEXT MONTH: Part 18 - Pressure Relief and Safety Devices used in the Vapour Compression Refrigeration Cycle

 

With thanks to Mike Creamer of Business Edge who revisits his Masterclass series of articles, updating and adding to the information which proved so useful to readers when the series was first published over ten years ago. In this reincarnation, the series will cover both air conditioning and refrigeration and serve as an on-going source of technical reference for experienced personnel as well as providing a solid educational grounding for newcomers to our industry.

 

The IOR Annual Conference – a conference on-demand

Delegates to the IOR Annual Conference taking place from 21 to 22 April will get the chance to access the event live and all sessions and recordings for up six months afterwards providing fantastic value and allowing anyone registering for the event ...

  01-Apr-2021

Thunder: the full inverter reversible R290 heat pump from 40 to 85 kW

Thunder is the newest solution from Clivet, designed with full-inverter technology on latest-generation scroll compressors and axial fans....

  24-Apr-2024

Customised Consulting TM44 Inspection Services

Customised Consulting are accredited to provide TM44 Inspection Services ((also known as Air Conditioning Energy Assessments (ACEA)) for both simple (level 3) and complex (level 4) systems for buildings and can provide competitive quotes in Weybridge, Surrey, Sussex, London and Kent.
  25-Apr-2024
ACR News is the number one magazine in the air conditioning and refrigeration industry. Don’t miss out, subscribe today!
Subcribe to ACR News

Diary

BESA National Conference