Published on 12 - June - 2012

Don't use valves with brazed-in nozzles on ammonia systems, says IoR


UK: THE Institute of Refrigeration has recommended that valves, where the valve nozzles are brazed into the main body, should not be used on ammonia refrigeration plant.

This latest safety alert comes as an update to a guidance note issued in May last year. It follows an incident in 2010 when a refrigeration engineer received severe burns from an unexpected ammonia release at a food distribution warehouse.

While the original guidance note blamed the incident on corrosion, further recent failures of this type of valve suggest that this is not the only cause. The IoR reports that the assembly of the valve is susceptible to lack of complete fusion of the brazing filler ring, which in turn weakens the joint of the side port to the valve body.

"The Institute of Refrigeration recommends that all such valves, where the valve nozzles are brazed into the main body, should not be used on ammonia refrigeration plant," says the update.

It further says that any valves fitted to existing systems should be carefully examined. If there is any doubt as to their integrity they should be replaced immediately with a suitable valve manufactured with a one-piece body, and should be treated with extreme care until they are replaced.

"This should include clearly labelling the valve with a warning, protecting it from accidental mechanical impact and using appropriate PPE when working on the system in the vicinity of the valve," it concludes.

In the original incident at a distribution warehouse in 2010, the refrigeration engineer received severe burn injuries when a significant amount of refrigerant was suddenly released while he was in the process of removing a valve cap from a DN 15 (½") charging valve. The valve was installed on the low pressure side of an ammonia system.

The engineer was using a check spanner to hold the body of the valve whilst undoing the cap with another spanner but even so the valve connection to the plant failed.

It was concluded that the failure was due to corrosion under the preformed brazing filler metal thus weakening the joint on to the valve parent metal. The corrosion had started externally and that forces exerted in fitting the valves, removing caps or fitting charging lines etc, may have damaged the valve.


Get all the week’s industry news and jobs direct to your inbox: click here to receive the free ACR-News.com weekly newsletter.

 Make a comment?


Your name
Subject

Inform me of responses to this comment

This Is CAPTCHA Image
Enter number above (anti-spam)



RSS Feeds
ACR-news.com News - RSS Feed All latest
ACR-news.com News - RSS Feed News
ACR-news.com Products - RSS Feed Products
ACR-news.com Suppliers - RSS Feed Suppliers
ACR-news.com Quizzes - RSS Feed Quiz
ACR-news.com Jobs - RSS Feed Jobs
Datateam is a modern and dynamic communications business with a product portfolio covering six business-to-business and healthcare sectors. Established in 1988, we have expanded over the years and now offer over 50 publications, websites, events and awards.
Post this story
 
Click here to receive the ACR-news.com weekly newsletter

Cookies

We use cookies to make this site as useful as possible. They are small text files we put in your browser to track and assist usage of our site but, with the exception of cookies that help you log in, they don't tell us who you are.
You can control cookies in your browser settings. If you use our site it implies that you consent to our cookie usage. To find out more about how we use cookies and how you can control them, click here to see our cookie policy.